Digital Output with Shutdown Input LB6108A

LB6108A
  • 8-channel
  • Outputs Ex ib
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Module can be exchanged under voltage
  • Galvanic group isolation
  • Line fault detection (LFD)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Folhas de dados: Dados técnicos do  LB6108A

Slots
Occupied slots2
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power dissipation2.35 W
Power consumption2.35 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Digital output
Number of channels8
Suitable field devices
Field deviceSolenoid Valve
Field device [2]audible alarm
Field device [3]visual alarm
Connectionchannel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16-
Current limit8 mA
Open loop voltage20 V
Line fault detectioncan be switched on/off for each channel via configuration tool
Test current0.33 mA
Short-circuit< 300 Ω
Open-circuit> 50 kΩ
Response time20 ms (depending on bus cycle time)
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Indicators/settings
LED indicationLED green: supply
LED red: line fault , communication error red flashing
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-78
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Altitudemax. 2000 m
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 160 g
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
EU-type examination certificatePTB 03 ATEX 2042 X
MarkingEx-Hexagon II (2) G [Ex ib Gb] IIC
Ex-Hexagon II (2) D [Ex ib Db] IIIC
Ex-Hexagon I (M2) [Ex ib Mb] I
Output
Voltage28 V
Current13.5 mA
Power376 mW (rectangular characteristic curve)
CertificatePF 08 CERT 1234 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Galvanic isolation
Output/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020
EN 60079-11:2012
EN 60079-15:2010
International approvals
ATEX approvalPF 08 CERT 1234 X
PTB 03 ATEX 2042 X
IECEx approval
IECEx certificateIECEx BVS 09.0037X
IECEx markingEx nA [ib Gb] IIC T4 Gc
[Ex ib Db] IIIC
[Ex ib Mb] I
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210101
ECLASS 11.027210101
ECLASS 10.0.127210101
ECLASS 9.027210101
ECLASS 8.027210101
ECLASS 5.127210120
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: LB6108A

Datasheet: LB6108A

DatasheetTipo de ArquivoTamanho do Arquivo
Datasheet LB6108APDF772 KB
Datenblatt LB6108APDF774 KB

Documents: LB6108A

ManualsTipo de ArquivoTamanho do Arquivo
ManualPDF5367 KB
HandbuchPDF5387 KB
Instruction manuals
ИнструкцииPDF177 KB
Instruction manual / BetriebsanleitungPDF344 KB
Návod k poużitíPDF171 KB
Instruktions manualPDF171 KB
Instruction manualPDF177 KB
KasutusjuhendPDF166 KB
KäyttöohjePDF166 KB
Manuel d'instructionsPDF175 KB
BetriebsanleitungPDF179 KB
Οδηγίες χρήσηςPDF182 KB
HandleidingPDF172 KB
Instruction manual / BetriebsanleitungPDF169 KB
Használati útmutatóPDF173 KB
Manuale di istruzioniPDF172 KB
Lietošanas pamācībaPDF170 KB
Instrukciju vadovasPDF172 KB
Instrukcja obsługiPDF174 KB
Manual de instruçõesPDF173 KB
Manual de utilizarePDF171 KB
Návod na poużitiePDF172 KB
Navodila za uporaboPDF169 KB
Manual de instruccionesPDF174 KB
ManualPDF169 KB
Application reports
Application Report - Communication Redundancy for Uninterrupted OperationPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesPDF208 KB
Application Report - Space Saving Extension for Existing PlantsPDF300 KB
Application Report - The Modern Whiskey DistilleryPDF176 KB
Application Report - Use of Remote I/O in Fluidized Bed SystemsPDF222 KB
Application Report - Using Remote I/O Systems for the Efficient Digitalization of PlantsPDF371 KB
Applikationsbericht - Die moderne Whiskey-BrennereiPDF130 KB
Applikationsbericht - Einsatz von Remote-I/O-Modulen in WirbelschichtanlagenPDF222 KB
Applikationsbericht - Platzsparende Erweiterung für bestehende AnlagenPDF300 KB
Applikationsbericht - Redundanz der Kommunikation für ungestörten BetriebPDF530 KB
Applikationsbericht - Remote-I/O-Systeme Typ LB und FB für digitale Anbindung analoger FeldgerätePDF208 KB
Applikationsbericht - Remote-I/O-Systeme für effiziente AnlagendigitalisierungPDF365 KB
Documents
Functional Safety ManualPDF2422 KB
Selection table - Solenoid driver/valve combinationsPDF299 KB
Auswahltabelle - Kombination Ventil - SteuerbausteinPDF300 KB
Handbuch funktionale SicherheitPDF2435 KB

CAD+CAE: LB6108A

EPLANTipo de ArquivoTamanho do Arquivo
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ177 KB
EPLAN macros LB-System / EPLAN-Makros LB-SystemZIP65808 KB
Gateway PROFINET

O nosso gateway LB/FB PROFINET abre as possibilidades para aplicações IIoT 4.0 nas indústrias de processos.